30 CFR § 56.4201 Inspection.
Table C-1 Hydrostatic Test Intervals for Fire Extinguishers
+-------------------------------------------------+----------+
| | Test |
| Extinguisher type | interval |
| | (years) |
+-------------------------------------------------+----------+
| Soda Acid.......................................| 5 |
| Cartridge-Operated Water and/or Antifreeze......| 5 |
| Stored-Pressure Water and/or Antifreeze.........| 5 |
| Wetting Agent...................................| 5 |
| Foam............................................| 5 |
| AFFF (Aqueous Film Forming Foam)................| 5 |
| Loaded Stream...................................| 5 |
| Dry-Chemical with Stainless Steel Shells........| 5 |
| Carbon Dioxide..................................| 5 |
| Dry-Chemical, Stored Pressure, with Mild | |
| Steel Shells, Brazed Brass Shells, | |
| or Aluminum Shells.............................| 12 |
| Dry-Chemical, Cartridge or Cylinder | |
| Operated, with Mild Steel Shells...............| 12 |
| Bromotrifluoromethane Halon 1301................| 12 |
| Bromochlorodifluoromethane Halon 1211...........| 12 |
| Dry-Powder, Cartridge or Cylinder-Operated, | |
| with Mild Steel Shells1........................| 12 |
+-------------------------------------------------+----------+
|
|
|