Appendix I

LIST OF FIGURES
Figure
No.
Title
1 Portable power cable ampacities--600 volts.
2 Portable cord ampacities--600 volts.
3 Portable power cable ampacities--601 to 5,000 volts.
4 Normal diameter of round cables with tolerances in
inches--600 volts.
5 Nominal dimension of flat cables with tolerances in
inches--600 volts.
6 Nominal diameter of heavy jacketed cords with
tolerances in inches--600 volts.
7 Nominal diameter of three-conductor portable power
cables with tolerances in inches--601 to 5,000 volts.
8 Fuse ratings or instantaneous settings of circuit
breakers for short-circuit protection of portable cables.
9 Specifications for portable cables longer than 500 feet.





      TABLE 1--PORTABLE POWER CABLE AMPACITIES--600 VOLTS (AMPERES PER
       CONDUCTOR BASED ON 60° C. COPPER TEMPERATURE--40° C. AMBIENT)

 +------------------+-----------+---------------+---------------+-----------+-----------+-----------+
 | Conductor size-- |  Single   | 2-conductor,  | 3-conductor,  |    4-     |    5-     |    6-     |
 |    AWG or MCM    | conductor | round or flat | round or flat | conductor | conductor | conductor |
 +------------------+-----------+---------------+---------------+-----------+-----------+-----------+
 | 8................|        45 |            40 |            35 |        30 |        25 |        20 |
 | 6................|        60 |            50 |            50 |        40 |        35 |        30 |
 | 4................|        85 |            70 |            65 |        55 |        45 |        35 |
 | 3................|        95 |            80 |            75 |        65 |        55 |        45 |
 | 2................|       110 |            95 |            90 |        75 |        65 |        55 |
 | 1................|       130 |           110 |           100 |        85 |        75 |        65 |
 | 1/0..............|       150 |           130 |           120 |       100 |        90 |        80 |
 | 2/0..............|       175 |           150 |           135 |       115 |       105 |        95 |
 | 3/0..............|       205 |           175 |           155 |       130 |       120 |       110 |
 | 4/0..............|       235 |           200 |           180 |       150 |       140 |       130 |
 | 250..............|       275 |           220 |           200 |       160 |...........|...........|
 | 300..............|       305 |           240 |           220 |       175 |...........|...........|
 | 350..............|       345 |           240 |           235 |       190 |...........|...........|
 | 400..............|       375 |           280 |           250 |       200 |...........|...........|
 | 450..............|       400 |           300 |           270 |       215 |...........|...........|
 | 500..............|       425 |           320 |           290 |       230 |...........|...........|
 +------------------+-----------+---------------+---------------+-----------+-----------+-----------+





          TABLE 2--PORTABLE CORD AMPACITIES--600 VOLTS (AMPERES PER
       CONDUCTOR BASED ON 60° C. COPPER TEMPERATURE--40° C. AMBIENT)

           +------------------+-----------+-----------+-----------+
           | Conductor size-- |    1-3    |    4-6    |    7-9    |
           |                  | conductor | conductor | conductor |
           +------------------+-----------+-----------+-----------+
           | 14...............|        15 |        12 |         8 |
           | 12...............|        20 |        16 |        11 |
           | 10...............|        25 |        20 |        14 |
           +------------------+-----------+-----------+-----------+




    TABLE 3--PORTABLE POWER CABLE AMPACITIES--601 TO 5,000 VOLTS (AMPERES
     PER CONDUCTOR BASED ON 75° C. COPPER TEMPERATURE--40° C. AMBIENT)

        +----------------------------+-------------+-------------+
        |                            | 3-conductor |     3-      |
        |                            |  types G-   |  conductor  |
        | Conductor size--AWG or MCM |   GC and    |  type SHD-  |
        |                            |   SIIC-GC   |  GC 2,001-  |
        |                            | 2,000 volts | 5,000 volts |
        +----------------------------+-------------+-------------+
        | 6..........................|          65 |          65 |
        | 4..........................|          85 |          85 |
        | 3..........................|         100 |         100 |
        | 2..........................|         115 |         115 |
        | 1..........................|         130 |         130 |
        | 1/0........................|         145 |         145 |
        | 2/0........................|         170 |         170 |
        | 3/0........................|         195 |         195 |
        | 4/0........................|         220 |         220 |
        | 250........................|         245 |         245 |
        | 300........................|         275 |         275 |
        | 350........................|         305 |         305 |
        +----------------------------+-------------+-------------+





                 TABLE 4--NOMINAL DIAMETERS OF ROUND CABLES
                    WITH TOLERANCES IN INCHES--600 VOLTS

 +-----------+-----------+--------------------------+-----------------------------+---------------+---------------+----------------------+
 |           |           |        2-conductor       |       3-conductor           |               |               |       6-conductor    |
 |           |           |----------|--------|---------|--------|---------|-------------|               |               |-----------|------------|
 |           |           |         |       |        |       |        |   Type     |               |               |          |           |
 | Conductor |   Single  |  Types  | Type  |  Type  | Type  |  Type  |  PCG, 3    | 4-conductor-- | 5-conductor-- |          |           |
 | size--AWG | conductor |  W & G  | PG, 2 | PCG, 3 | W & G | PG, 3  |   power,   |  Types W & G  |  Types W & G  |   Type w | Tolerance |
 | or MCM    |           | twisted | power | power, |       | power, | 2 control, |               |               |          |           |
 |           |           |         |       | ground |       | ground |   ground   |               |               |          |           |
 +-----------+-----------+---------+-------+--------+-------+--------+------------+---------------+---------------+----------+-----------+
 | 8.........|      0.44 |    0.81 |  0.84 |   0.94 |  0.91 |   0.93 |       1.03 |          0.99 |          1.07 |     1.18 |     ±0.03 |
 | 6.........|       .51 |     .93 |   .93 |    .98 |  1.01 |   1.03 |       1.18 |          1.10 |          1.21 |     1.31 |      ±.03 |
 | 4.........|       .57 |    1.08 |  1.08 |   1.10 |  1.17 |   1.20 |       1.29 |          1.27 |          1.40 |     1.52 |      ±.03 |
 | 3.........|       .63 |    1.17 |  1.17 |   1.20 |  1.24 |   1.27 |       1.31 |          1.34 |          1.48 |     1.61 |      ±.03 |
 | 2.........|       .66 |    1.27 |  1.27 |   1.29 |  1.34 |   1.34 |       1.39 |          1.48 |          1.61 |     1.75 |      ±.03 |
 | 1.........|       .74 |    1.44 |  1.44 |   1.44 |  1.51 |   1.52 |       1.52 |          1.68 |          1.88 |     2.05 |      ±.03 |
 | 1/0.......|       .77 |    1.52 |  1.52 |   1.52 |  1.65 |   1.68 |       1.68 |          1.79 |          1.96 |     2.13 |      ±.04 |
 | 2/0.......|       .82 |    1.65 |  1.65 |   1.65 |  1.75 |   1.79 |       1.79 |          1.93 |          2.13 |     2.32 |      ±.04 |
 | 3/0.......|       .87 |    1.77 |  1.77 |   1.77 |  1.89 |   1.93 |       1.93 |          2.07 |          2.26 |     2.49 |      ±.05 |
 | 4/0.......|       .93 |    1.92 |  1.92 |   1.92 |  2.04 |   2.13 |       2.13 |          2.26 |          2.46 |     2.71 |      ±.05 |
 | 250.......|      1.03 |    2.16 |  2.16 |   2.16 |  2.39 |   2.39 |       2.39 |          2.66 |...............|..........|      ±.06 |
 | 300.......|      1.09 |    2.32 |.......|........|  2.56 |........|............|          2.84 |...............|..........|      ±.06 |
 | 350.......|      1.15 |    2.43 |.......|........|  2.68 |........|............|          2.98 |...............|..........|      ±.06 |
 | 400.......|      1.20 |    2.57 |.......|........|  2.82 |........|............|          3.14 |...............|..........|      ±.06 |
 | 450.......|      1.26 |    2.67 |.......|........|  2.94 |........|............|          3.26 |...............|..........|      ±.06 |
 | 500.......|      1.31 |    2.76 |.......|........|  3.03 |........|............|          3.40 |...............|..........|      ±.06 |
 +-----------+-----------+---------+-------+--------+-------+--------+------------+---------------+---------------+----------+-----------+






                 TABLE 5--NOMINAL DIMENSIONS OF FLAT CABLES
                    WITH TOLERANCES IN INCHES--600 VOLTS

 +-----------+---------------------------------------------------------------------------+-------------------------------------+
 |           |                             2-conductor                                   |           3-conductor--Type G       |
 |           |--------------------------------------|--------------------------------------|-------------------|-------------------|
 | Conductor |               Type W                |               Type G                |       Major      |       Minor      |
 | size--AWG |-------------------|-------------------|-------------------|-------------------|-------|------------|-------|------------|
 |           |    Major         |     Minor        |      Major       |       Minor      |      |           |      |           |
 |           |-------|------------|-------|------------|-------|------------|-------|------------| O.D. | Tolerance | O.D. | Tolerance |
 |           | O.D. | Tolerance | O.D. | Tolerance | O.D. | Tolerance | O.D. | Tolerance |      |           |      |           |
 +-----------+------+-----------+------+-----------+------+-----------+------+-----------+------+-----------+------+-----------+
 | 8         | 0.84 |     ±0.04 | 0.51 |     ±0.03 |......|...........|......|...........|......|...........|......|...........|
 | 6         |  .93 |      ±.04 |  .56 |      ±.03 | 1.02 |      ±.04 | 0.56 |      ±.03 | 1.65 |     ±0.06 | 0.67 |     ±0.05 |
 | 4         | 1.05 |      ±.04 |  .61 |      ±.03 | 1.15 |      ±.04 |  .61 |      ±.03 | 1.85 |      ±.06 |  .75 |      ±.05 |
 | 3         | 1.14 |      ±.04 |  .68 |      ±.03 | 1.26 |      ±.04 |  .68 |      ±.03 | 1.99 |      ±.06 |  .77 |      ±.05 |
 | 2         | 1.24 |      ±.04 |  .73 |      ±.03 | 1.35 |      ±.04 |  .73 |      ±.06 | 2.10 |      ±.06 |  .81 |      ±.05 |
 | 1         | 1.40 |      ±.04 |  .81 |      ±.03 | 1.55 |      ±.04 |  .81 |      ±.03 | 2.43 |      ±.06 |  .97 |      ±.05 |
 | 1/0       | 1.51 |      ±.04 |  .93 |      ±.03 | 1.67 |      ±.04 |  .93 |      ±.03 |......|...........|......|...........|
 | 2/0       | 1.63 |      ±.04 |  .99 |      ±.03 | 1.85 |      ±.04 |  .99 |      ±.03 |......|...........|......|...........|
 | 3/0       | 1.77 |      ±.04 | 1.03 |      ±.03 | 2.00 |      ±.04 | 1.03 |      ±.03 |......|...........|......|...........|
 | 4/0       | 1.89 |      ±.04 | 1.10 |      ±.03 | 2.10 |      ±.04 | 1.10 |      ±.03 |......|...........|......|...........|
 +-----------+------+-----------+------+-----------+------+-----------+------+-----------+------+-----------+------+-----------+






                TABLE 6--NOMINAL DIAMETERS OF HEAVY JACKETED
                 CORDS WITH TOLERANCES IN INCHES--600 VOLTS

 +-----------+----------------------+----------------------+----------------------+----------------------+----------------------+----------------------+
 |           |     2-conductor      |     3-conducter      |     4-conducter      |     5-conducter      |     6-conductor      |     7-conductor      |
 | Conductor |-----------|------------|-----------|------------|-----------|------------|-----------|------------|-----------|------------|-----------|------------|
 | size--AWG | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance | Diameter | Tolerance |
 +-----------+----------+-----------+----------+-----------+----------+-----------+----------+-----------+----------+-----------+----------+-----------+
 | 14........|     0.64 |     ±0.02 |     0.67 |     ±0.02 |     0.71 |     ±0.02 |     0.78 |     ±0.03 |     0.83 |     ±0.03 |     0.89 |     ±0.03 |
 | 12........|      .68 |      ±.02 |      .72 |      ±.03 |      .76 |      ±.03 |      .83 |      ±.03 |      .89 |      ±.03 |      .98 |      ±.03 |
 | 10........|      .73 |      ±.03 |      .80 |      ±.03 |      .84 |      ±.03 |      .90 |      ±.03 |     1.00 |      ±.03 |     1.07 |      ±.03 |
 +-----------+----------+-----------+----------+-----------+----------+-----------+----------+-----------+----------+-----------+----------+-----------+






           TABLE 7--NOMINAL DIAMETERS OF THREE-CONDUCTOR PORTABLE
         POWER CABLES WITH TOLERANCES IN INCHES--601 TO 5,000 VOLTS

 +------------------+----------------------+----------------------+------------------------+------------------------+
 |                  |      Type G-GC       |    Type SHC-GC       |       Type SHD-GC      |       Type SHD-GC      |
 |                  | (nonshielded) 2,000  | (shielded overall)   | (individually shielded | (individually shielded |
 | Conductor size-- |        volts         |     2,000 volts      |    power conductors)   |    power conductors)   |
 |    AWG or MCM    |-----------|------------|-----------|------------|    2,001-3,000 volts   |    3,001-5,000 volts   |
 |                  |          |           |          |           |------------|-------------|------------|-------------|
 |                  | Diameter | Tolerance | Diameter | Tolerance |  Diameter | Tolerance  |  Diameter | Tolerance  |
 +------------------+----------+-----------+----------+-----------+-----------+------------+-----------+------------+
 | 6................|     1.25 |    +0.10, |          |           |           |            |           |            |
 |                  |          |     -0.06 |     1.39 |    +0.11, |           |            |           |            |
 |                  |          |           |          |     -0.07 |      1.62 |    +0.13,  |           |            |
 |                  |          |           |          |           |           |     -0.08  |      1.78 |    +0.14,  |
 |                  |          |           |          |           |           |            |           |     -0.09  |
 | 4................|     1.40 | +.11,-.07 |     1.55 | +.12,-.08 |      1.77 | +.14,-.09  |      1.90 | +.15,-.10  |
 | 3................|     1.48 | +.12,-.07 |     1.62 | +.13,-.08 |      1.84 | +.15,-.09  |      1.98 | +.16,-.10  |
 | 2................|     1.55 | +.12,-.08 |     1.71 | +.14,-.09 |      1.92 | +.15,-.10  |      2.09 | +.17,-.11  |
 | 1................|     1.74 | +.14,-.09 |     1.89 | +.15,-.09 |      2.04 | +.16,-.10  |      2.18 | +.17,-.11  |
 | 1/0..............|     1.84 | +.15,-.09 |     2.02 | +.16,-.10 |      2.18 | +.17,-.11  |      2.34 | +.19,-.12  |
 | 2/0..............|     1.99 | +.16,-.10 |     2.16 | +.17,-.11 |      2.29 | +.18,-.12  |      2.46 | +.20,-.12  |
 | 3/0..............|     2.12 | +.17,-.11 |     2.30 | +.18,-.11 |      2.45 | +.20,-.12  |      2.62 | +.21,-.13  |
 | 4/0..............|     2.30 | +.18,-.12 |     2.48 | +.20,-.12 |      2.62 | +.21,-.13  |      2.76 | +.22,-.14  |
 | 250..............|     2.46 | +.20,-.12 |     2.70 | +.22,-.13 |...........|............|...........|............|
 | 300..............|     2.63 | +.21,-.13 |     2.84 | +.23,-.14 |...........|............|...........|............|
 | 350..............|     2.75 | +.22,-.14 |     2.97 | +.24,-.15 |...........|............|...........|............|
 +------------------+----------+-----------+----------+-----------+-----------+------------+-----------+------------+






     TABLE 8--FUSE RATINGS OR INSTANTANEOUS SETTING OF CIRCUIT BREAKERS
         FOR SHORT-CIRCUIT PROTECTION OF PORTABLE CABLES AND CORDS

     +------------------+-----------+-------------+--------------------+
     |                  |           |  Maximum    | Maximum allowable  |
     | Conductor size-- |    Ohms/  |  allowable  |  circuit breaker   |
     |    AWG or MCM    | 1,000 ft. | fuse rating |   instantaneous    |
     |                  | at 25° C. | (amperes)   | setting (amperes)1 |
     +------------------+-----------+-------------+--------------------+
     | 14...............|      2.62 |          20 |                50  |
     | 12...............|      1.65 |          30 |                75  |
     | 10...............|      1.04 |          40 |               150  |
     | 8................|      .654 |          80 |               200  |
     | 6................|      .410 |         100 |               300  |
     | 4................|      .259 |         200 |               500  |
     | 3................|      .205 |         250 |               600  |
     | 2................|      .162 |         300 |               800  |
     | 1................|      .129 |         375 |             1,000  |
     | 1/0..............|      .102 |         500 |             1,250  |
     | 2/0..............|      .081 |.............|             1,500  |
     | 3/0..............|      .064 |.............|             2,000  |
     | 4/0..............|      .051 |.............|             2,500  |
     | 250..............|      .043 |.............|             2,500  |
     | 300..............|      .036 |.............|             2,500  |
     | 350..............|      .031 |.............|             2,500  |
     | 400..............|      .027 |.............|             2,500  |
     | 450..............|      .024 |.............|             2,500  |
     | 500..............|      .022 |.............|             2,500  |
     +------------------+-----------+-------------+--------------------+




1 Higher circuit-breaker settings may be permitted for special applications when justified.





TABLE 9--SPECIFICATIONS FOR PORTABLE CABLES LONGER THAN 500 FEET1

    +------------------+---------------+------------------+---------------+
    |                  |               | Normal ampacity  | Resistance at |
    |                  |      Max.     | at 60° C. copper | 60° C. copper |
    | Conductor size-- |   allowable   | temperature (40° |  temperature  |
    |    AWG or MCM    | length (feet) |   C. ambient)    |    (ohms)     |
    +------------------+---------------+------------------+---------------+
    | 6................|           550 |               50 |         0.512 |
    | 4................|           600 |               70 |          .353 |
    | 3................|           650 |               80 |          .302 |
    | 2................|           700 |               95 |          .258 |
    | 1................|           750 |              110 |          .220 |
    | 1/0..............|           800 |              130 |          .185 |
    | 2/0..............|           850 |              150 |          .157 |
    | 3/0..............|           900 |              175 |          .130 |
    | 4/0..............|         1,000 |              200 |          .116 |
    | 250..............|         1,000 |              220 |          .098 |
    | 300..............|         1,000 |              240 |          .082 |
    | 350..............|         1,000 |              260 |          .070 |
    | 400..............|         1,000 |              280 |          .061 |
    | 450..............|         1,000 |              300 |          .054 |
    | 500..............|         1,000 |              320 |          .050 |
    +------------------+---------------+------------------+---------------+


1 Fuses shall not be used for short-circuit protection of these cables. Circuit breakers shall be used with the instantaneous trip settings not to exceed the values given in Table 8.

[33 FR 4660, Mar. 19, 1968; 33 FR 6345, Apr. 26, 1968, as amended at 42 FR 8373, Feb. 10, 1977]




Back to Top   Back to Top www.msha.gov www.dol.gov


Mine Safety and Health Administration (MSHA)
1100 Wilson Boulevard, 21st Floor
Arlington, VA 22209-3939
Phone:    (202) 693-9400
Fax-on-demand: (202) 693-9401
Technical (web) questions: Webmaster
On-line Filing Help: MSHAhelpdesk@dol.gov
or call (877) 778-6055

Contact Us