Petition
for Modification
In the matter
of
Canyon Fuel Company, LLC
Skyline Mine No. 3 Mine
I.D. No.
42-01566
Docket No.
M-2002-118-C
30 CFR 75.507
PROPOSED DECISION AND ORDER
On December 12, 2002, a petition
was filed seeking a modification of the application of 30 CFR 75.507 to
Petitioner's Skyline Mine No. 3 located in Carbon County, Utah. Petitioner on January 6, 2003, submitted an
amended petition of the application of 30 CFR 75.507. The Petitioner alleges that the alternative method outlined in
the petition will at all times guarantee no less than the same measure of
protection afforded by the standard.
MSHA personnel conducted an
investigation of the petition and filed a report of their findings and
recommendations with the Administrator for Coal Mine Safety and Health. After a careful review of the entire record,
including the petition, comments and MSHA's investigative report and
recommendation, this Proposed Decision and Order is issued.
Finding of Fact and Conclusion of Law
The alternative method proposed
by the Petitioner (as amended by the recommendations of MSHA investigators)
will at all times guarantee no less than the same measure of protection
afforded the miners under 30 CFR 75.507.
On the basis of the petition and
the findings of MSHA's investigation, Canyon Fuel Company, LLC, is granted a
modification of the application of 30 CFR 75.507 to its Skyline Mine No. 3.
ORDER
Wherefore, pursuant to the
authority delegated by the Secretary of Labor to the Administrator for Coal
Mine Safety and Health, and pursuant to Section 101(c) of the Federal Mine
Safety and Health Act of 1977, 30 U.S.C., sec. 811(c), it is ordered that
Canyon Fuel Company, LLC's Petition for Modification of the application of 30
CFR 75.507 in the Skyline Mine No. 3 is hereby:
GRANTED, for the use of 4,160-volt, three phase,
alternating current submersible pumps installed
in boreholes in the Skyline Mine No. 3, conditioned upon
compliance with the following
terms and
conditions:
1. The 4,160-volt, three phase,
alternating-current electric power circuit for the pump
must be
designed and installed to:
(a) Contain either a direct or derived
neutral which must be grounded
through a suitable resistor at the source transformer or power
center,
and
a grounding circuit originating at the grounded side of the
grounding resistor, must extend along with the power conductors
and
serve as the grounding conductor for the frame of the pump. No other
electric equipment shall be supplied
power from this circuit.
(b) Contain a grounding resistor which
limits the ground-fault current to not
more than 3.75
amperes. The grounding resistor must be rated for the
maximum fault current available and must be insulated from ground for
a voltage equal to the phase-to-phase voltage of the system.
(2) The following protections for the 4,160
volt pump circuit must be provided by a
suitable circuit interrupting device of adequate interrupting
capacity with devices to
provide protection against undervoltage, grounded phase,
short-circuit, and
overload.
(1)
The undervoltage protection device must operate on
a loss of voltage to prevent
automatic
restarting of the equipment.
(2)
The grounded phase protection device must be set not to
exceed 40 percent of the current rating of the neutral grounding resistor.
(3)
The pump power circuit must be provided witha "Look Ahead" circuit device to prevent closing the circuit
breaker when a phase to ground fault condition exists on the system.
(4)
The short circuit protection device must be set to not
exceed the required short circuit protection for the 4,160 volt pump motor, or
75 percent of the minimum available phase to phase short circuit current. Whichever is the smallest.
(e) Contain a disconnecting
device located on the surface and installed in conjunction with the circuit
breaker to provide visual evidence that the power is disconnected.
(5)
The disconnecting device must include a means to visually
determine the 4,160-volt pump power circuit is disconnected, and provided with
a means to lock, tag-out and ground the system.
(6)
The disconnecting device must be designed to prevent entry
unless the disconnect handle is in the off position and the circuit is
grounded.
(7)
The disconnecting device must be clearly identified and
provided with warning signs, stating "Danger do not enter unless the circuit is
opened, locked, tagged-out, and grounded."
(3) The 4,160 volt pump power system must
include a fail-safe ground check circuit or
other no less effective device approved by the Secretary which shall
cause the
circuit
breaker to open when either the ground or pilot wire is broken. A
manually
operated test switch must be provided to verify the operation of the
ground check
device.
(4) The incoming high voltage three-phase
alternating current system must be provided with a low
resistance
grounding medium for the grounding of the lightning/surge arresters for the
high-
voltage
pump power circuits that is separated from the mine neutral grounding medium by
a
distance of not less than 25 feet.
(5) The pump electric
control circuit must be designed and installed so that:
(a) The pump cannot start in either the
manual or automatic mode if the
water is below the low
water probe level.
(b) When the water level is lower than the
low water probe, the pump will
cease operation.
(c) When the water level reaches the high
water probe, the pump will start
operation.
(d) The low water probe must be located
above the motor and electrical
connections of the
pump. The low water probe
must be located not
less than three (3) feet above the water pump.
(5)
The high and low water probes must consistof redundant electronic
pressure transducers that are suitable for submersible pump control
application.
(6)
All probe circuits are protected by an MSHAapproved intrinsically safe barriers.
(7)
The grounded-phase protective circuitcan be tested by injecting a test current
through the grounded-phase current transformer.
(8)
A soft-start motor controller must be providedand used for pump startup and shutdown.
The controller must include automatic controls forphase loss, over current, and locked
rotor/short circuit protection.
(1)
A radio remote telemetry system can be usedto monitor motor current.
The telemetry
system
can include the capability for manual startup andshutdown of the pump.
The
telemetry
system must preclude the capability to reset the system when any fault condition
exists on the system.
7.
The surface pump control and power circuits must be examined
as required by 30 CFR 77.502.
8. The armored power cable to the submersible
pump motor must be suitable for this application
and
have a current carrying capacity not less than 125 percent of the full load
motor current of the
submersible
pump motor and an outer jacket suitable for a "wet location".
The
armored power cable must be supported at the entrance to the borehole and
throughout its
length
by securing it with clamps, spaced approximately 20 feet apart, affixed to the
discharge
pipe casing.
1.
The pump installations must comply with all other applicable
30 CFR requirements.
2.
Any 30 CFR 75.507 pumps installed at the Skyline Mine No. 3
after this petition is granted must be approved by the District Manager before
they are put in operation.
11. Within 60 days
after this Petition for Modification is granted, the Petitioner shall submit
proposed revisions for their approved 30 CFR Part 48 training plan to the Coal
Mine Safety and Health District Manager.
These proposed revisions shall specify initial and refresher training
regarding the alternative method outlined in the petition and the terms and
conditions stated in the Proposed Decision and Order.
The
procedures of 30 CFR 48.3 for approval of proposed revisions to already
approved training plans shall apply.
Any party to this action desiring a hearing on this mattermust file in
accordance with 30 CFR 44.14, within 30 days, a request with the Administrator
for Coal Mine Safety and Health, 1100 Wilson Boulevard, Arlington, Virginia 22209-3939.
If a hearing
is requested, the request shall contain a concise summary of position on the
issues of fact or law desired to be raised by the party requesting the hearing,
including specific objections to the proposed decision. A party other than Petitioner who has
requested a hearing shall also comment upon all issues of fact or law presented
in the petition, and any party to
this action
requesting a hearing may indicate a desired hearing site. If no request for a hearing is filed within 30
days after service thereof, the Decision and Order will become final and must
be posted by the operator on the mine bulletin board at the mine.
_____________________________
John F. Langton
Acting Deputy Administrator
for Coal Mine Safety and Health
|