Skip to main content
U.S. flag

An official website of the United States government.

Petition - Docket No. 2002-118-C

Petition for Modification

In the matter of

Canyon Fuel Company, LLC

Skyline Mine No. 3 Mine

I.D. No. 42-01566

Docket No. M-2002-118-C

30 CFR 75.507

PROPOSED DECISION AND ORDER

On December 12, 2002, a petition was filed seeking a modification of the application of 30 CFR 75.507 to Petitioner's Skyline Mine No. 3 located in Carbon County, Utah.  Petitioner on January 6, 2003, submitted an amended petition of the application of 30 CFR 75.507.  The Petitioner alleges that the alternative method outlined in the petition will at all times guarantee no less than the same measure of protection afforded by the standard.

MSHA personnel conducted an investigation of the petition and filed a report of their findings and recommendations with the Administrator for Coal Mine Safety and Health.  After a careful review of the entire record, including the petition, comments and MSHA's investigative report and recommendation, this Proposed Decision and Order is issued. 

Finding of Fact and Conclusion of Law

The alternative method proposed by the Petitioner (as amended by the recommendations of MSHA investigators) will at all times guarantee no less than the same measure of protection afforded the miners under 30 CFR 75.507. 

On the basis of the petition and the findings of MSHA's investigation, Canyon Fuel Company, LLC, is granted a modification of the application of 30 CFR 75.507 to its Skyline Mine No. 3.

ORDER

Wherefore, pursuant to the authority delegated by the Secretary of Labor to the Administrator for Coal Mine Safety and Health, and pursuant to Section 101(c) of the Federal Mine Safety and Health Act of 1977, 30 U.S.C., sec. 811(c), it is ordered that Canyon Fuel Company, LLC's Petition for Modification of the application of 30 CFR 75.507 in the Skyline Mine No. 3 is hereby: 

GRANTED, for the use of 4,160-volt, three phase, alternating current submersible pumps installed in boreholes in the Skyline Mine No. 3, conditioned upon compliance with the following terms and conditions: 

1. The 4,160-volt, three phase, alternating-current electric power circuit for the pump must be designed and installed to:

(a) Contain either a direct or derived neutral which must be grounded through a suitable resistor at the source transformer or power center, and a grounding circuit originat­ing at the grounded side of the grounding resistor, must extend along with the power conductors and serve as the grounding conductor for the frame of the pump.  No other Electric equipment shall be supplied power from this circuit.

(b) Contain a grounding resistor which limits the ground-fault current to not more than 3.75 amperes.  The grounding resistor must be rated for the maximum fault current available and must be insulated from ground for a volt­age equal to the phase-to-phase voltage of the system.

(2) The following protections for the 4,160 volt pump circuit must be provided by a suitable circuit interrupting device of adequate interrupting capacity with devices to provide protection against undervoltage, grounded phase, short-circuit, and overload.

(a)  The undervoltage protection device must operate on a loss of voltage to prevent automatic restarting of the equipment. 

(b) The grounded phase protection device must be set not to exceed 40 percent of the current rating of the neutral grounding resistor.

(c) The pump power circuit must be provided with a "Look Ahead" circuit device to prevent closing the circuit breaker when a phase to ground fault condition exists on the system.

(d) The short circuit protection device must be set to not exceed the required short circuit protection for the 4,160 volt pump motor, or 75 percent of the minimum available phase to phase short circuit current.  Whichever is the smallest.

(e) Contain a disconnecting device located on the surface and installed in conjunction with the circuit breaker to provide visual evidence that the power is disconnected.

(f) The disconnecting device must include a means to visually determine the 4,160-volt pump power circuit is disconnected, and provided with a means to lock, tag-out and ground the system.

(g) The disconnecting device must be designed to prevent entry unless the disconnect handle is in the off position and the circuit is grounded.

(h) The disconnecting device must be clearly identified and provided with warning signs, stating "Danger do not enter unless the circuit is opened, locked, tagged-out, and grounded."

(i) The 4,160 volt pump power system must include a fail-safe ground check circuit or other no less effective device approved by the Secretary which shall cause the circuit breaker to open when either the ground or pilot wire is broken.  A manually operated test switch must be provided to verify the operation of the ground check device. 

(j) The incoming high voltage three-phase alternating current system must be provided with a low resistance grounding medium for the grounding of the lightning/surge arresters for the high-voltage pump power circuits that is separated from the mine neutral grounding medium by a distance of not less than 25 feet.

(3) The pump electric control circuit must be designed and installed so that:

(a) The pump cannot start in either the manual or automatic mode if the water is below the low water probe level.

(b) When the water level is lower than the low water probe, the pump will cease operation.

(c) When the water level reaches the high water probe, the pump will start operation.

(d) The low water probe must be located above the motor and electrical connections of the pump.  The low water probe must be located not less than three (3) feet above the water pump.

(4) The high and low water probes must consist of redundant electronic pressure transducers that are suitable for submersible pump control application. 

(5) All probe circuits are protected by an MSHA approved intrinsically safe barriers.

(6) The grounded-phase protective circuit can be tested by injecting a test current through the grounded-phase current transformer.

(7) A soft-start motor controller must be provided and used for pump startup and shutdown.   The controller must include automatic controls for phase loss, over current, and locked rotor/short circuit protection.

(8) A radio remote telemetry system can be used to monitor motor current.  The telemetry system can include the capability for manual startup and shut down of the pump.  The telemetry system must preclude the capability to reset the system when any fault condition exists on the system. 

9. The surface pump control and power circuits must be examined as required by 30 CFR 77.502.

10. The armored power cable to the submersible pump motor must be suitable for this application and have a current carrying capacity not less than 125 percent of the full load motor current of the submersible pump motor and an outer jacket suitable for a "wet location".

The armored power cable must be supported at the en­trance to the borehole and throughout its length by securing it with clamps, spaced approximately 20 feet apart, affixed to the discharge pipe casing.

(a) The pump installations must comply with all other appli­cable 30 CFR requirements.

(b) Any 30 CFR 75.507 pumps installed at the Skyline Mine No. 3 after this petition is granted must be approved by the District Manager before they are put in operation.

11. Within 60 days after this Petition for Modification is granted, the Petitioner shall submit proposed revisions for their approved 30 CFR Part 48 training plan to the Coal Mine Safety and Health District Manager.  These proposed revisions shall specify initial and refresher training regarding the alternative method outlined in the petition and the terms and conditions stated in the Proposed Decision and Order.

The procedures of 30 CFR 48.3 for approval of proposed revisions to already approved training plans shall apply.

Any party to this action desiring a hearing on this matter must file in accordance with 30 CFR 44.14, within 30 days, a request with the Administrator for Coal Mine Safety and Health, 1100 Wilson Boulevard, Arlington, Virginia 22209-3939. 

If a hearing is requested, the request shall contain a concise summary of position on the issues of fact or law desired to be raised by the party requesting the hearing, including specific objections to the proposed decision. A party other than Petitioner who has requested a hearing shall also comment upon all issues of fact or law presented in the petition, and any party to this action requesting a hearing may indicate a desired hearing site.  If no request for a hearing is filed within 30 days after service thereof, the Decision and Order will become final and must be posted by the operator on the mine bulletin board at the mine.

 

 

 

 

_________________________________

John F. Langton

Acting Deputy Administrator

 for Coal Mine Safety and Health