August 9, 2024 Fatality - Fatality Alert

Lapse in Appropriations

For workplace safety and health, please call 800-321-6742; for mine safety and health, please call 800-746-1553; for Job Corps, please call 800-733-5627 and for Wage and Hour, please call 1-866-487-9243 (1 866-4-US-WAGE).  This website is currently not being updated due to the suspension of Federal government services. The last update to the site was 10/1/2025.  Updates to the site will start again when the Federal government resumes operations.

Accident Report: Fatality Reference

MINE FATALITY – On August 9, 2024, an electrician was seriously injured by an arc flash from a 4,160 VAC circuit while working on an electrical panel for a motor control center.  On August 22, 2024, he died from his injuries.

Accident scene where an electrician was seriously injured by an arc flash from a 4,160 VAC circuit while working on an electrical panel for a motor control center. 

Best Practices

  • Lock out and tag out circuits before working on electrical equipment:
    • Identify and control all hazardous energy sources before starting any task.
    • Open the circuit breaker or load break switch to de-energize the equipment. 
    • Open the visual disconnect to confirm that incoming power is off.
    • Lockout/Tagout the visual disconnect.
    • Ground the de-energized conductors.
  • Use properly rated electrical meters and personal protective equipment, such as electrically rated gloves, arc flash protection suits, insulated blankets or mats, and polycarbonate barriers. 
  • Establish safe procedures before beginning work and discuss them with all miners involved in the task.

Additional Information

This is the 15th fatality reported in 2024, and the second classified as “Electrical.”